Video: How do you wire and program status relays R1 and R2 on an ATV320 drive?

Article available in these languages:

Resolution:

The ATV320 drive includes two programmable relays:

  • R1 (Relay 1)

    • Can be wired as:
      • Normally Open (NO): R1A – R1C
      • Normally Closed (NC): R1B – R1C
  • R2 (Relay 2)

    • Normally Open (NO) only

Follow these steps from the drive interface:

  1. Navigate to: CONF (Configuration menu)
  2. Select: FULL
  3. Go to: I-O (Input/Output menu)
  4. Choose:
    • R1 to configure Relay 1, or
    • R2 to configure Relay 2

You can customize relay behavior based on your application, including:

  • Assigned function (e.g., run status, fault indication)
  • Activation condition
  • Delay time
  • Hold time
  • Fallback behavior
Refer to the product documentation for detailed parameter descriptions. Watch the next video for further information about wiring and programming.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Attachment(s)

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.