How can we help you today?
Video: How do you wire and program status relays R1 and R2 on an ATV320 drive?
Resolution:
The ATV320 drive includes two programmable relays:
-
R1 (Relay 1)
- Can be wired as:
- Normally Open (NO): R1A – R1C
- Normally Closed (NC): R1B – R1C
- Can be wired as:
-
R2 (Relay 2)
- Normally Open (NO) only
Follow these steps from the drive interface:
- Navigate to: CONF (Configuration menu)
- Select: FULL
- Go to: I-O (Input/Output menu)
- Choose:
- R1 to configure Relay 1, or
- R2 to configure Relay 2
You can customize relay behavior based on your application, including:
- Assigned function (e.g., run status, fault indication)
- Activation condition
- Delay time
- Hold time
- Fallback behavior
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Released for: Schneider Electric USA
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.