Video: How does the LK70AN neutral/ground lug install into QO or Homeline load centers?
Issue:
Product Design Features
Product Line:
QO or Homeline Load Centers
Resolution:
The LK70AN branch neutral/ground lug will install on one of the branch neutral bars on the load center interior or can be installed on a PK__GTA ground bar installed in the load center.
The LK70AN will mount under two(2) wire binding screws on the bar and will accept (1) #12 - Al or (1) #14 - 4 Cu wire.
The attached video is ONLY to supplement the INSTRUCTIONS that come with the kit. PLEASE make sure to read the instructions and all the below Safety Information that is located in the instructions BEFORE working on any electrical equipment.
A PDF copy of the complete instructions is attached below the video.

Make sure to turn OFF ALL Power supplying the equipment and verify the power is OFF using a properly rated voltage sensing device, BEFORE working on or with electrical equipment.
1) Once all Safety steps are followed, begin the kit installation by following the instructions.
2) Remove Cover from load center.
NOTE: When load center is NOT used as Service Equipment neutral assembly is NOT bonded/grounded.
3) Install neutral lug A ONLY in neutral bar B as shown in figures 1 or 2 of the instructions.
NOTE: When load center is used as Service Equipment
4) Neutral Lug A maybe installed in any two neutral bar terminals B.
5) Loosen 2 terminal screws C in neutral bar B and insert both tangs of the neutral lug A into the 2 wire holes of the neutral bar.
6) Position as shown in the instructions and secure with the same two terminal screws to 30 lb-in (3.4 N-m)
NOTE: PLEASE READ ALL INSTRUCTIONS AND SAFETY INFORMATION THAT COME WITH THE KIT AND NEVER WORK ON ENERGIZED EQUIPMENT.
Product Design Features
Product Line:
QO or Homeline Load Centers
Resolution:
The LK70AN branch neutral/ground lug will install on one of the branch neutral bars on the load center interior or can be installed on a PK__GTA ground bar installed in the load center.
The LK70AN will mount under two(2) wire binding screws on the bar and will accept (1) #12 - Al or (1) #14 - 4 Cu wire.
The attached video is ONLY to supplement the INSTRUCTIONS that come with the kit. PLEASE make sure to read the instructions and all the below Safety Information that is located in the instructions BEFORE working on any electrical equipment.
A PDF copy of the complete instructions is attached below the video.
Make sure to turn OFF ALL Power supplying the equipment and verify the power is OFF using a properly rated voltage sensing device, BEFORE working on or with electrical equipment.
1) Once all Safety steps are followed, begin the kit installation by following the instructions.
2) Remove Cover from load center.
NOTE: When load center is NOT used as Service Equipment neutral assembly is NOT bonded/grounded.
3) Install neutral lug A ONLY in neutral bar B as shown in figures 1 or 2 of the instructions.
NOTE: When load center is used as Service Equipment
4) Neutral Lug A maybe installed in any two neutral bar terminals B.
5) Loosen 2 terminal screws C in neutral bar B and insert both tangs of the neutral lug A into the 2 wire holes of the neutral bar.
6) Position as shown in the instructions and secure with the same two terminal screws to 30 lb-in (3.4 N-m)
NOTE: PLEASE READ ALL INSTRUCTIONS AND SAFETY INFORMATION THAT COME WITH THE KIT AND NEVER WORK ON ENERGIZED EQUIPMENT.
Released for: Schneider Electric USA
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.