How can we help you today?
Where can you wire in a shutdown circuit on the ATV660 enclosed drives?
Issue:
Wire a shut down circuit on the ATV660 enclosed drives.
Product Line:
ATV660
Environment:
All
Cause:
Wants to wire in a Normally closed contact and shut down the drive if the contact opens.
Resolution:
You can remove the jumper between terminals 1 and 2 now you can wire in your normally closed contact between terminals 1 and 2.
Please note this is not your normal start and stop circuit. The normal start and stop for drive control is terminals 3 and 4.
Wire a shut down circuit on the ATV660 enclosed drives.
Product Line:
ATV660
Environment:
All
Cause:
Wants to wire in a Normally closed contact and shut down the drive if the contact opens.
Resolution:
You can remove the jumper between terminals 1 and 2 now you can wire in your normally closed contact between terminals 1 and 2.
Please note this is not your normal start and stop circuit. The normal start and stop for drive control is terminals 3 and 4.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.