Are the Altivar Process Drives suitable for use on ungrounded, corner grounded and hi leg Delta systems?
The drive can operate on corner grounded and high leg voltage systems. However, the built-in EMC filter must be disconnected. For High leg, the neutral must not be used.
The VFD can also operate on an ungrounded delta system but the EMC filter must also be disconnected.
Note that certain models of some Altivar drive families do not have an EMC filter installed so there will be nothing to disconnect.
Please consult the latest version of the Installation Manual for your specific Altivar drive model for details.