Is the mechanical interlock for reversing contactor pairs LC1D5010/LC1D5001/LC1D5011 compatible with the new LC1D50A?

Issue:
Identify the compatibility between the mechanical interlocks for reversing contactor LC1D50A and LC1D5011.

Product Line:
TeSys™ D Reversing Contactors

Environment:
IEC Contactors and Starters

Resolution:
No, they are not compatible. Mechanical interlocks are only compatible within the same contactor series.

LA9D4002 mechanical interlock is used for LC1D5011, LC1D5001, LC1D5010
LAD9R3 mechanical interlock is used for LC1D50A