How can we help you today?

What are the default settings for the serial communication port on a LINK 150?

Issue:
User would like to know what the default settings are for the serial port on a Link150 Gateway.

Product Line:
Link150 (EGX150)

Environment:
Ethernet Gateways

Cause:
User may want to configure his daisy chain of devices to match that of the default settings for the Link150

Resolution:

See table below  for Serial Port Settings

Description

Settings

Mode

Master

Physical Interface

RS-485 2-Wire

Transmission Mode

Automatic

Baud Rate

19200 bps

Parity

Even

Stop bits

Auto

Termination

Enabled

Biasing

Enabled

Response Timeout

3 seconds

Remote Device Connections

Feature used only for Link150 in slave Mode

Port

502


Documentation: EcoStruxure Link 150

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings