Why does ATV212 Remote Keypad (VW3A1101) switches to Frequency if screen not touched and goes dim, even though Custom RPM display has been set up?

Issue:
ATV212 Remote Keypad switches to Frequency even though Custom RPM display has been set up

Resolution:
This can happen if F702 =0 so need to set F702=60 for one pair of motor poles.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.