What breakers are available to be DIN rail mounted?
Issue:
Can breakers be DIN rail mounted?

Product line:
Circuit Breakers

Resolution:
The following breakers can be mounted on 35 mm DIN rail as standard:
  • QOU breakers
  • Multi 9 breakers
  • Powerpact B-frame breaker
The Powerpact H- and J-frame breakers are also DIN rail mountable, but require the S29305 DIN rail mounting kit. The kit is not compatible with 2 pole HD and HG breakers. This kit requires 15 mm depth on a 35 mm DIN rail. See the attached document or visit this link for the instruction bulletin.

Schneider Electric USA

Attachment(s)
Din Adapter 48940-239-01.pdf [117.99 KB]