How can we help you today?

Does a 5.0P or 5.0H trip unit have a ground fault alarm indicator on the LED display screen?

Issue:
Is there a ground fault alarm indicator on the trip unit itself?

Product Line:
Circuit breakers

Environment:
Micrologic 5.0P and 5.0H trip units

Resolution:
No, there is not an indicator on the trip unit itself. Also, the trip unit LCD screen gives no indication when the ground-fault pickup has been reached.  The GF alarm can only be indicated by:
1) sending the signal through the M2C or M6C contact block, or
2) reading the GF alarm through Modbus Register if available.  See FA306313 for more information on reading ground-fault alarm through Modbus.
3) trip unit alarm history (wrench button, go to history logs, then scroll to alarm history)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings