Power Monitoring Expert 8.2 - Configuring the Audible Alert for Unacknowledged Alarms

Issue:
In Power Monitoring Expert 8.2, the behavior of the audible alert in the Web Application Alarms tab is configurable. A user can choose to have an audible alert only when there are Active alarms present, or when there are Unacknowledged alarms. By default, only Active alarms will generate an audible alert.

Product Line:
Power Monitoring Expert 8.2

Environment:
Web Applications
Alarms
SQL Server Management Studio

Resolution:
*Warning: Irreparable database damage can occur. This procedure should only be performed by users familiar with SQL Server Management Studio. Databases should be backed up prior to performing this procedure.*


1) Open the attached .sql file in SQL Server Management Studio
2) Configure the 'SET Value =' to the desired behavior.

'true' = This will activate Audible alerts when there are Unacknowledged alarms.
'false' = This will activate Audible alerts only when there are Active alarms (default setting).


The Application Modules services do not need to be restarted after the query is executed as the change is picked up automatically.

Note: This article applies only to Power Monitoring Expert 8.2. In Power Monitoring Expert 9.0, the behavior of the audible alerts is now configurable in the Web Applications under Settings > Alarm Views

Recommendation

If you are using an older version of PME, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.com

PME support information

Schneider Electric USA

Attachment(s)

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.