How can ATVLogic programming be transferred from one ATV320 drive to another and what tools do I need?

Resolution:
ATVLogic programming can be transferred between ATV320 drives using either of the following tools:

  • Multi-Loader: Version 3.17 or later
  • Simple Loader: Version 1.7 or later
  • SoMove

These tools can transfer the ATV320 configuration, including the ATVLogic program.

Before starting the transfer:

  1. Ensure the ATV320 drive is stopped.
  2. Verify that the Function Block Status (FbSt) is set to Stop.
    d

    If the FB status is Run, you must change FB Command (FbCd) to Stop.
    d
  3. Perform the configuration transfer using the appropriate Multi-Loader or Simple Loader procedure.

To export the ATVLogic program using SoMove:

  1. Ensure the Function Block Status is set to Stop.
  2. Connect to the ATV320 in online mode using SoMove.
  3. Open the ATVLogic tab.
  4. Select Device > ATVLogic > Export.
    ATVLogic_SoMove
  5. Save the ATVLogic file.
  6. Connect to the destination ATV320 and import the saved file.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.