PME Installer fails at 'Configure Maintenance Account' step during Configure System step
Issue
When attempting to perform an in-place upgrade or a reconfigure, the installer fails at the 'Configure Maintenance Account' step.
MethodHandler encountered a problem while calling 'Security.Configuration.ProductLoginHelper.CreateUpdateProductLogin': System.Reflection.TargetInvocationException: Exception has been thrown by the target of an invocation. ---> System.DirectoryServices.AccountManagement.PrincipalOperationException: This operation is disallowed as it could result in an administration account being disabled, deleted or unable to logon.
---> System.Runtime.InteropServices.COMException: This operation is disallowed as it could result in an administration account being disabled, deleted or unable to logon.
Product Line
Power Monitoring Expert 2024
Power Monitoring Expert 2023
Power Monitoring Expert 2022
Power Monitoring Expert 2021
Power Monitoring Expert 9.x
Power Monitoring Expert 8.x
Power Monitoring Expert 7.2.x
Environment
PME In Place Upgrades and Reconfigures
Local Users and Groups
Cause
The IONMaintenance account already exists from a previous installation of SPM or PME. If the user is on a domain they may have password restriction policies that prevent the local account from changing passwords for other users that belong to the " or that the password complexity does not meet standards of the organization.
Resolution
1. Open the 'Local Users and Groups' window by clicking on the start menu and typing 'lusrmgr.msc'.
2. Click on 'Users'.
3. Highlight the 'IONMaintenance' account, right-click and select 'Properties'.
4. Click on the 'Member of' tab and remove 'Administrators'
5. Click on 'OK' for changes to take effect.
** Ensure that the 'IONMaintenance' account is restored as part of the 'Administrators' group following the successful configuration in order for PME scheduled tasks to run successfully.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.