How can we help you today?

Video: How to configure the "DIAGNOSE Mode" of “RENF22R2MMW NFC Timing Relay” product using smart phone?

Article available in these languages:

Step 1 : Product Identification
Step 1.1 Initiate the NFC App
Step 1.2 Select the Read button
Step 1.3 Place the phone in front of NFC Timing Relay.
And adjust the phone until the “Pairing Indication LED” lit-up.
Step 1.4 Below screen appeared when Uploading is successfully executed.

Step 2 : Function & Timing selection
Step 2.1 Select the Function C. Off-delay relay with control signal
Step 2.2 Press the T button and set T = 35s

Step 3 : Loading the DIAGNOSE Mode
Step 3.1 Select <Diagnose> button.
Step 3.2 Press the Read button. Place the phone in front of NFC Timing Relay.
Step 3.3 Below message appeared after Uploading is successfully executed.
Step 3.4 4 - Power Supply Indication (green) LED
Fast Blinking….
to indicate that the product is on <DIAGNOSE> Mode.


Schneider Electric USA

Attachment(s)

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.