What is the maximum current consumption on the internal +24vdc power supply on the ATV630 and ATV930 Process drives?
Issue:
Current consumption of the internal +24V DC power supply for the Altivar Process Drives ATV630/930
Product Line:
Altivar ATV630 and Altivar 930
Environment:
All
Cause:
Want to know if they can use the drives built in +24vdc power supply to power up a PLC card.
Resolution:
24V Output power supply for digital inputs and safety
function STO inputs O = +24 Vdc
Tolerance: minimum 20.4 Vdc, maximum 27 Vdc
Current: maximum 200 mA for both 24 Vdc terminals
Terminal protected against overload and short-circuit
In Sink Ext position, this supply is powered by external PLC supply
Current consumption of the internal +24V DC power supply for the Altivar Process Drives ATV630/930
Product Line:
Altivar ATV630 and Altivar 930
Environment:
All
Cause:
Want to know if they can use the drives built in +24vdc power supply to power up a PLC card.
Resolution:
24V Output power supply for digital inputs and safety
function STO inputs O = +24 Vdc
Tolerance: minimum 20.4 Vdc, maximum 27 Vdc
Current: maximum 200 mA for both 24 Vdc terminals
Terminal protected against overload and short-circuit
In Sink Ext position, this supply is powered by external PLC supply
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.