How can we help you today?

PowerSCADA Operation (PSE/PSO) Alarm Filter Tree not appearing in runtime

Issue
When opening the Alarms page within the PSE runtime, the Alarm Filter Tree on the left side is blank and does not populate with the expected groups.

Product Line
PSE 8.1, 8.2
PSO 9.2

Environment
Runtime

Cause
The Report Server is what builds the Alarm Filter Tree.

Resolution
Add a Report Server to the PSE/PSO project and re-compile. Navigate away and back to the Alarm page and the Alarm Filter Tree should populate. Restarting project runtime is not required.

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.