How do I disable a logic section in Control Expert (formerly Unity)?

Issue:

How do I disable a logic section in Control Expert (formerly Unity)?

Product Line:

Logic Section, Control Expert, Unity Pro

Resolution:

Step 1: Right click on Section Name in the Browser
Step 2: Select Properties
Step 3: Select the Condition Tab
Step 4: Select a variable name from the Data Editor or create a new variable. When the variable is turned on or off you'll see a green Icon or a red Icon next to the section name indicating the section is solving (green) or its
being disabled (red)


If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.