How many S908 (140CRA31908) networks are permitted in an M580 ERIO application?
Issue:
How many S908 (140CRA31908) networks are permitted in an M580 ERIO application?
Product Line:
140CRA31908
Resolution:
You can have one S908 network in an M580 application. (140CRA31908).
If you're using M580 HSBY you are allowed a second 140CRA31908 in order to achieve redundancy on the RIO network.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.