What can cause a "M/S Warning" error on the ATV930 drive that can not be cleared?

Cause:
Issue with the client / Server set up

Resolution:
indeed on both (client and Server) configurations, there is "M/S Device Warning (MSDA)".
This alarm is raised:
- On Client, when at least one Server is not present whereas the Client  was running or is waiting to start.
- On Server, when Client device is not present whereas the Server was running.

To avoid this warning, first power-on the Client then the Server. It will work as follow:
1 - Client  is powered-on; its warning is on as the Server is power-off.
2 - Server is powered-on; its warning is off as the Client is detected.
3 - Server is in "RUN"; the warning of the client is off.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)


Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.