Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can NQ Panelboard with QO breakers be used on a 125V DC Application?
Issue:
Can an NQ panelboard be used on a 125V DC application?

Product Line:
NQ panelboards sold and supported in the USA.

Issue:
Application

Cause:
Selection

Resolution:
Circuit breaker engineering has self  certified  QO/QOB breakers up to 70A/3P maximum to 125V DC.  Enter the panel as factory assembled in product selectors as 48V DC.  Place a note in Notes to Engineering to have Peru label the panel as 125V DC.   However, the breakers do not have UL certification as they have never been UL tested to this voltage.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings