How can we help you today?
What would cause the ATV61 drive mounted inside a MCC to show a PRA drive status only when the HOA is in auto mode?
Issue:
What would cause the ATV61 drive mounted inside a MCC to show a PRA status?
Product Line:
ATV61 MCC
Environment:
All with HOA
Cause:
HOA was miswired PWR input was wired to LI3 auto manual and HOA was wired to PWR input
Resolution:
Troubleshoot this circuit by checking the status of PWR input. In this case the HOA was wired in error to the PWR input. So the Drive is Rdy in hand and off but goes to PWR when they switch to Auto.
Moved the wire from LI3 to PWR and from PWR to LI3
Now it works.
What would cause the ATV61 drive mounted inside a MCC to show a PRA status?
Product Line:
ATV61 MCC
Environment:
All with HOA
Cause:
HOA was miswired PWR input was wired to LI3 auto manual and HOA was wired to PWR input
Resolution:
Troubleshoot this circuit by checking the status of PWR input. In this case the HOA was wired in error to the PWR input. So the Drive is Rdy in hand and off but goes to PWR when they switch to Auto.
Moved the wire from LI3 to PWR and from PWR to LI3
Now it works.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.