How can we help you today?

Can a Masterpact breaker be remotely reset after a fault if it has a spring charging motor and shunt close?

Issue:
Is there anything else needed besides a spring charging motor and shunt close to reset a Masterpact breaker remotely after a fault?

Product Line:
Power Circuit Breakers

Resolution:
You would also need either automatic or remote reset capability. Each of these options can be ordered with the breaker. When the breaker trips on a fault, there is a red reset button located right above the trip unit that pops out. That button must be pressed back in before the breaker can be reset. The automatic reset option prevents the button from popping out on a fault. The remote reset option allows a control voltage to be delivered that will retract the button so that the breaker can be reset. The remote reset option is also available field installed with the following numbers:

NT Fixed:
120 V control voltage: S47344
240 V control voltage: S47345

NT Drawout:
120 V control voltage: S47434
240 V control voltage: S47435

NW Fixed:
120 V control voltage: S48202
240 V control voltage: S48203

NW Drawout:
120 V control voltage: S48472
240 V control voltage: S48473

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.