Video: How to replace a Micrologic trip unit on a PowerPacT™ P frame, R frame, or Masterpact NT or NW breaker
Issue:
How to replace a Micrologic trip unit on a PowerPacT™ P-frame, R-frame, or Masterpact NT or NW Breaker
Product Line:
Molded Case Circuit Breakers
Resolution:
NOTE: The ET1.0I trip units are NOT replaceable. Only the Micrologic trip units (3.0, 5.0, 3.0A, 5.0A, 6.0A, 5.0P, 6.0P, 5.0H, and 6.0H) are replaceable. Also, note that if you are replacing a 3.0 or 5.0 trip unit with an ammeter, power, or harmonic trip unit, you will also need to order the green 12-pin connector (kit S33101 for Masterpact, S33100 for PowerPacT™).
First, remove the accessory cover. After doing so, remove the 12-pin connector (if one is installed) on the top of the trip unit. Then loosen the top and bottom screws of the trip unit, and slide it out. Slide the new/replacement trip unit back in its place, and re-tighten the screws. Reinstall or install the new 12-pin connector (if needed). For more information, see the attached instruction bulletin or the instructional video below:
How to replace a Micrologic trip unit on a PowerPacT™ P-frame, R-frame, or Masterpact NT or NW Breaker
Product Line:
Molded Case Circuit Breakers
Resolution:
NOTE: The ET1.0I trip units are NOT replaceable. Only the Micrologic trip units (3.0, 5.0, 3.0A, 5.0A, 6.0A, 5.0P, 6.0P, 5.0H, and 6.0H) are replaceable. Also, note that if you are replacing a 3.0 or 5.0 trip unit with an ammeter, power, or harmonic trip unit, you will also need to order the green 12-pin connector (kit S33101 for Masterpact, S33100 for PowerPacT™).
First, remove the accessory cover. After doing so, remove the 12-pin connector (if one is installed) on the top of the trip unit. Then loosen the top and bottom screws of the trip unit, and slide it out. Slide the new/replacement trip unit back in its place, and re-tighten the screws. Reinstall or install the new 12-pin connector (if needed). For more information, see the attached instruction bulletin or the instructional video below:
Released for: Schneider Electric USA
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.