What can cause an error 153 in Somove or INFM 22 error on the ATV930 drives?
Resolution:
This is due to Ethernet crash ( a new correction is implemented in Ethernet Stack on new drive V1.3IE05 ). Also we got this if ATV9xx is supplied only to external 24V ( Power supplied is OFF) and 24V used is not stable (goes from 24V to 8v then 24), some time the drive trips in INFM. It would be suggested that updating to new firmware version 1.3 or above could fix the issue if the problem keeps coming back.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)