How can we help you today?

What coil reference is needed to replace the coil in a LC1F1700P7 TeSys F range contactor?

For the TeSys F contactor LC1F1700P7, the coil is not supplied as a single component. This contactor uses a dual‑coil design, meaning that the replacement requires two identical coil modules.

To replace the coil, you must order:

  • 2 × LX1FK110 coil references

Both coils must be installed together to ensure correct operation of the contactor.

Additional information and recommendations:

  • The LC1F1700P7 is a high‑power TeSys F contactor, and its control system relies on two synchronized coils for proper closing and holding of the contacts.
  • Always replace both coils at the same time, even if only one appears faulty, to maintain balanced performance and avoid uneven wear or malfunction.
  • Ensure the replacement coils have the same control voltage (110 V AC in this case – “P7”) as the original contactor specification.
  • Before installation, isolate the equipment and follow standard safety procedures.
  • After replacement, verify correct wiring and perform a functional test of the contactor.

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.