What is the AIC rating, and breaker type of a SASFB subfeed breaker kit used in the Square D Speed D switchboard?
Issue:
What type of circuit breakers and AIC ratings are used in the SASFB type subfeed breaker kits for the Speed D switchboards?
Product Line:
Switchboard
Environment:
Speed D
Resolution:
The SASFB subfeed breaker kits use the HJ and JJ frame breakers and they are rated for 65KAIC at 240V and 480V.