Why does an ATV12 not power up or display anything on the screen?

Resolution:
If the ATV12 display is blank, the drive may not be receiving power, or it may have an internal hardware fault.

Troubleshooting Steps

  1. Verify the incoming mains voltage at terminals L1, L2, and L3.
  2. Measure the DC bus voltage to confirm the drive is receiving and converting power correctly.
  3. Check the control terminal DC power supplies for the correct voltage levels.
  4. Inspect the +24 VDC supply on the control terminals. If external devices are connected, disconnect them temporarily and check whether one of them is pulling down the power supply.
  5. If the drive remains inoperative after these checks, the ATV12 may have an internal hardware failure.

Note: Replacement parts are not available for the ATV12 drive. If the unit is confirmed to be faulty, the recommended solution is to replace the drive.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.