Can the Altistarts and Altivar sotstarters ATS48, ATS22, ATS480 be controller via Modbus as well use remote HMI at the same time?

Remote panel as well as PLC with modbus - both represents modbus masters.
Modbus communication from its principle does not support two masters.
The best solution to share one slave (ATS) between two masters (PLC and HMI) is to use modbus port multiplexer. This device alternates modbus requests, once between ATS and PLC and second time between HMI and ATS and so on.
See attached files for more info about PXP-314MB port multiplexer.

Schneider Electric USA

Attachment(s)
PXP314MB.zip [3.77 MB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings