Video: How Do You Change the Control Terminal Type from Sink to Source or from Source to Sink on an ATV61 or ATV71 Drive?

Resolution:

The control terminal type on an ATV61 or ATV71 drive can be changed by adjusting the SW1 DIP switch located on the control terminal card.

Procedure

  1. Open the cover on the drive's front control panel to access the control terminals.
  2. Loosen the locking screw until the spring is fully extended.
  3. Slide the control terminal card downward and remove it from the drive.
  4. Locate the SW1 DIP switch on the card.
  5. Move the DIP switch to the desired position:
    • Source mode
    • Sink mode
  6. Reinstall the control terminal card by sliding it back into place.
  7. Tighten the locking screw to secure the card.
  8. Close the control panel cover.

Important Note

Always verify that the SW1 switch position matches the intended control wiring method (source or sink) before returning the drive to service.


SW1

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings