What configuration is required for an ATV320 drive when used on an ungrounded IT system?

Resolution:

When an ATV320 drive is used in an ungrounded IT system (isolated or impedance-grounded neutral) or a corner-grounded system, it is mandatory to disconnect the internal EMC filter to prevent improper operation, overvoltage, or overheating.

The procedure to disable the EMC filter depends on the drive model and voltage rating:


For 230 V drives, 400/460 V B-version drives, and 400/460 V C-version drives up to 4.0 kW, refer to the document:
“IT grounding ground screw removal.pdf”, which explains how to remove the grounding screw for the EMC filter.


For models ATV320U55N4C to ATV320D15N4C, refer to the document:
“IT_Jumper_ATV320_N4C.pdf”, which details the jumper method used to disable the EMC filter.


Important: Failure to disconnect the EMC filter in IT or corner-grounded systems may result in overvoltage, overheating, or equipment damage.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)


Schneider Electric USA

Attachment(s)
IT grounding ground screw disable.pdf [942.97 KB]
IT Jumper_ ATV320_N4C.pdf [315.15 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings