How do you configure a Freewheel Stop and a Run Permissive on ATV32 and ATV320 drives?

Resolution:

You can configure both a Freewheel Stop (instead of a ramp stop) and a Run Permissive input directly from the drive keypad by following the steps below.


Configure Freewheel Stop (Always Active)

To set the drive so it always performs a Freewheel Stop:

  1. Press the dial on the keypad.
  2. Navigate to:
    ConF → FULL → FUn- → Stt → Stt
  3. Set the parameter to nSt.

This ensures the drive performs a freewheel stop rather than a ramp stop.


Configure Run Permissive Input

To assign a Run Permissive using a digital/logic input:

  1. Press the dial on the keypad.
  2. Navigate to:
    ConF → FULL → FUn- → Stt → nSt
  3. Assign nSt to the desired Logic/Digital Input (DIx / LIx).

The drive will only be allowed to run when this input is in the correct state.


Important Notes

  • Freewheel Stop (nSt) is an active-low input.
  • If the assigned input is not wired, the drive will remain locked in the nSt state and will not run.
  • Until the actual permissive contact is installed, add a jumper from 24 V to the assigned DIx/LIx input to allow the drive to run.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.