How Do I Configure an Altivar 630 (ATV630) for 2-Wire Control and Connect the Start/Stop Signal?

Resolution:
To configure the ATV630 for 2-wire control:

  1. From the drive keypad, go to 5 – Complete Settings.
  2. Select 5.5 – Command and Reference.
  3. Locate 2/3 Wire Type and set it to 2 Wire.

Start/Stop Wiring:

  • Connect the drive's 24 VDC supply to DI1 through a normally open, maintained contact.
  • Contact closed: The drive receives a Forward Run command.
  • Contact open: The Forward Run command is removed, and the drive stops according to the configured stop mode.

If the drive does not respond to the Start/Stop command:

  • Check the top-right corner of the drive HMI. It should display TERM, indicating that the drive is configured to receive commands from the terminals.
  • Check the top-left corner of the HMI. RDY indicates that the drive is ready and waiting for a run command.
  • If TERM and RDY are displayed but the drive still does not respond, verify the drive's command and reference configuration.
  • Refer to the ATV600 Series Programming Manual and check the following parameters:
    • CHCF (Control Mode): Verify that the command configuration is appropriate for IO Mode
    • FR1 (Reference Frequency 1): Verify that the frequency reference is assigned to the intended source (analog inputs)
    • CD1 (Command channel 1): Verify that the command channel is set for terminals.

For additional configuration details and troubleshooting information, refer to the ATV600 Programing Manual.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.