How Do You Configure Preset Speeds on ATV630 and ATV930 Drives?

Resolution:

You can set preset speeds on ATV630 and ATV930 drives by assigning digital inputs and defining the corresponding speed values.

✅ Basic Setup Steps

  1. Go to:
    Main Menu → Complete Settings (CST) → Generic Functions → Preset Speeds

  2. Assign preset speed inputs:

    • Assign digital inputs (DIx) to preset speed selection (for example, DI1, DI2, DI3).
  3. Set the speed values:

    • Define each preset speed (e.g., SP2, SP3, SP4, etc.) in Hz based on your application.
  4. Activate preset speeds:

    • When the assigned digital inputs change state, the drive automatically switches to the corresponding preset speed.

Preset speeds are selected using a binary (ON/OFF) combination of digital inputs:

  • Each digital input represents a binary bit (0 = OFF, 1 = ON).
  • Up to 16 preset speeds are supported depending on the number of inputs configured.
  • The combination of ON/OFF states determines which preset speed is active.
  • Preset speeds override the normal speed reference when active.
  • Always verify input assignments to avoid unintended operation.

The manual contains a truth table that explains which inputs need to be On/Off for multiple Preset Speeds to work.  See the attached excerpt from the manual.

https://www.se.com/us/en/download/document/EAV64318/

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)


Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.