How can we help you today?

Can we have different DNP sever sessions to talk with different SCADA clients

Question:
Can we have different DNP sever sessions to talk with different SCADA clients. Cause customer has two SCADA clients & they have respective master/slave address.


Answer:
No.
DNP3 as TCP server only supports one session with one set of master/slave address.
So customer has to adjust the two clients as same master/slave address to talk with the common session in NOR.
If they would like two customized sessions at NOR part, two NOR modules are needed.

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.