How can we help you today?

What is the terminal lug data for ALL the 60 amp, US and Canada, Heavy Duty Safety Switches (for Example: CH362, CH362DS, CHU362AWK, H362, H362DS, HU362 etc.)?

Issue:

Product Features

Product Line:
Heavy Duty Safety Switches

Environment:
Main lug terminal data

Cause:
Application

Resolution:
The standard lug wire range for the 60A heavy duty safety switches is (1) #12 - #3 (AL) OR  (1) #14 - #3(CU).

NOTES:
1) 30 -100 A switches are suitable for 60 or 75 degree wires. EXCEPT the H60XBD and H60XBDAA use 75 degree CU wire ONLY. Use #6 AWG Copper Wire MAXIMUM for 60Amp Rating.
2) There are NO alternate lugs available, other than compression lugs and the compression lugs DO NOT allow for larger or more wires. See the Switch Wiring diagram or current On-Line Digests for Compression lug part numbers.


Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.