How can we help you today?

How to reset Altivar ATV212 variable speed drive showing an Error when controlled via Modbus?

If you can communicate with the drive while display shows error, then you can reset the drive fault over modbus using bit 13 of command word.
See attached page from ATV212 manual.
The fault of course must be "resetable". List of all resetable faults can be found in ATV212 programming manual.

Schneider Electric USA

Attachment(s)
Extracted pages from ATV212 Modbus_manual_EN_S1A53844_01.pdf [68.14 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings