Can you convert a Speed D Switchboard from a Meter Main to a Main only with no metering or remote metering?
Product Line:
Switchboard, SWBD
Environment:
Speed D Switchboard
Cause:
Application
Resolution:
The SA10BL bus link kit is used to connect the bussing, where a meter would normally be placed by the local utility. We already have a bus link installed in the C phase so you only require:
1 kit for 400A Speed D boards, and 2 kits for 600A and 800A Switchboards. Switchboards that require 2 kits per phase are assembled in series to complete the current path.
This option is nice when there are no utility requirements, you have a remote meter application, or just want a main only or a main and distribution.
The following video demonstrates how the SA10BL fits within a Speed-D switchboard:
Can you convert a Speed D Switchboard from a Meter Main to a Main only with no metering or remote metering?
Product Line:
Switchboard, SWBD
Environment:
Speed D Switchboard
Cause:
Application
Resolution:
The SA10BL bus link kit is used to connect the bussing, where a meter would normally be placed by the local utility. We already have a bus link installed in the C phase so you only require:
1 kit for 400A Speed D boards, and 2 kits for 600A and 800A Switchboards. Switchboards that require 2 kits per phase are assembled in series to complete the current path.
This option is nice when there are no utility requirements, you have a remote meter application, or just want a main only or a main and distribution.
The following video demonstrates how the SA10BL fits within a Speed-D switchboard:
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.