What would cause the ATV630 Ethernet IP option card VW3A3720 to not show up in somove under the Fieldbus A slot?
Issue:
Causes for an ATV630 Ethernet IP option card VW3A3720 to not show up in somove under the Fieldbus A slot.
Product Line:
ATV630 with
Environment:
All
Cause:
ATV630 drives firmware is not at 1.5 or greater or you may need to build a project offline and then import the program into Somove.
Resolution:
Checked option 1 and it shows Ethernet IP card. option 2 is no
Drive firmware is Version 1.5IEXX or greater which is good for the Ethernet IP option card.
Next Open up the Somove software:
Checked and we created a project offline adding the Ethernet IP card for option A
Now we copied the program from the drive and now it shows up as Ethernet IP under slot A in the Field bus section under Parameter list.
Causes for an ATV630 Ethernet IP option card VW3A3720 to not show up in somove under the Fieldbus A slot.
Product Line:
ATV630 with
Environment:
All
Cause:
ATV630 drives firmware is not at 1.5 or greater or you may need to build a project offline and then import the program into Somove.
Resolution:
Checked option 1 and it shows Ethernet IP card. option 2 is no
Drive firmware is Version 1.5IEXX or greater which is good for the Ethernet IP option card.
Next Open up the Somove software:
Checked and we created a project offline adding the Ethernet IP card for option A
Now we copied the program from the drive and now it shows up as Ethernet IP under slot A in the Field bus section under Parameter list.
Released for: Schneider Electric USA
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.