How can we help you today?

Why does an ATV6xx / ATV9xx show DC bus overvoltage when the incoming voltage is within normal range?

ATV600 or ATV900 drives if used on a corner grounded or resistance ground (IT) system may trip on DC Bus Overvoltage fault.

This is due to the design of the internal EMC filter.

When installed on this type of system the EMC filter should be disconnected.
Refer to the installation manual for your specific part number drive for changes to be made to the EMC filter connection when used on an IT or Corner Grounded system.

The method to disconnect varies by part number so please refer to the installation manual for specific instructions for your model number.

NOTE: if the drive powers on without the error, but then trips when attempting to run, check the motor for phase to phase or phase to ground issues.

*******

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions: Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance: Support | Schneider Electric Global (se.com)

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.