How does the Reset button work on the TeSys T?

Issue:
Identify the functioning of the TeSys T's reset button

Product Line:
IEC Overload Relays

Environment:
Products sold in the US

Cause:
Resetting a fault on an LTMR

Resolution:

The reset button on the front of the TeSys T LTMR controller can be used to reset a fault, perform a self test, return the device to factory default settings, or induce a fault.

To reset a fault press the button and release it within 3 seconds.
To perform a self test, Press and hold the button for 3 to 15 seconds.
To perform a Full Factory Reset of the Tesys, press and hold the button for 15 to 20 seconds. (This will clear the programming in the Tesys T and return the programming to 'factory new' state).
To generate a fault condition, press and hold the button for more than 20 seconds.  Note that a fault created by holding the Reset button in for more than 20 seconds will require a power cycle to reset.  It can not be reset by pressing the reset button and releasing it within 3 seconds.


Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings