How many auxiliary devices (Control Power Transformer or Voltage Transformer) can be placed in a structure of Square D Arc Resistant MasterClad Switchgear?
Issue:
Identify the amount of auxiliary devices that can be installed in Square D MasterClad Switchgears
Product Line:
Air-Insulated Switchgear
Environment:
MasterClad MV Switchgear
Resolution:
Two auxiliary devices (CPT – max 15kVA or VT) can be mounted in full height structure with no breakers. One auxiliary device (CPT – max 15kVA or VT) can be mounted in a structure above or below a breaker (max 2000A).
Identify the amount of auxiliary devices that can be installed in Square D MasterClad Switchgears
Product Line:
Air-Insulated Switchgear
Environment:
MasterClad MV Switchgear
Resolution:
Two auxiliary devices (CPT – max 15kVA or VT) can be mounted in full height structure with no breakers. One auxiliary device (CPT – max 15kVA or VT) can be mounted in a structure above or below a breaker (max 2000A).
Released for: Schneider Electric USA