ATV600/ATV900: How to Configure the Catch on the Fly Function
Resolution
The Catch on the Fly function is set to No by factory default.
To check or change the setting using the drive HMI:
- From the Main Menu, select Complete Settings and press OK.
- Select Error/Warning Handling and press OK.
- Scroll to Catch on the Fly and press OK.
- Select the desired setting:
- No – Catch on the Fly disabled
- Yes – Catch on the Fly enabled
- Press OK to confirm the selection.
- Press the Home button to return to the Main Menu.