What are the differences between Powerpact B-frame and H-frame?
Issue:
What is the advantage of using a B frame from an H frame?
Product Line:
Molded Case Circuit Breakers
Environment:
Powerpact B-Frame and H-frame Circuit Breakers
Resolution:
Powerpact B-frame
-available in 1, 2, 3, and 4 pole construction
-available up to 125A
-compatible with Everlink lugs
-rated 600Y/347V max. also covers 480 delta. Ex. BGL36100.
-also available in 480Y/277V max. (I-Line breaker only, with suffix "Y" and voltage code is 4 ,i.e. BGA34050Y)
Powerpact H-frame
-available in 2 and 3 pole construction only
-available up to 150A
-rated 600V delta.
What is the advantage of using a B frame from an H frame?
Product Line:
Molded Case Circuit Breakers
Environment:
Powerpact B-Frame and H-frame Circuit Breakers
Resolution:
Powerpact B-frame
-available in 1, 2, 3, and 4 pole construction
-available up to 125A
-compatible with Everlink lugs
-rated 600Y/347V max. also covers 480 delta. Ex. BGL36100.
-also available in 480Y/277V max. (I-Line breaker only, with suffix "Y" and voltage code is 4 ,i.e. BGA34050Y)
Powerpact H-frame
-available in 2 and 3 pole construction only
-available up to 150A
-rated 600V delta.
Released for: Schneider Electric USA
Explore more
Category:
Explore more
Category:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.