Why is my ATV630 drive not following the analog speed reference or ramping to speed?
Resolution:
Several factors can prevent the drive from following the analog speed reference or ramping correctly. Common causes include a missing or incorrect analog signal, improper configuration of the analog input type or range, or the drive referencing the wrong speed source. In some cases, preset speeds or other functions may override the analog input. Additionally, the drive may not be in the correct operating state, which can also prevent it from responding as expected.
1.- Verify the Analog Signal
- Go to I/O Map (4.10) → Analog Inputs Image.
- Confirm the drive is receiving the expected signal.
- Example: If 10V is sent to AI1, the display should show ~10V.
2.- Check Analog Input Configuration
- Navigate to:
Complete Settings → Input/Output → AI/AQ (Menu 5.11) - Ensure:
- Input type matches your signal (e.g., 0–10V or 4–20 mA).
- Minimum and maximum values are set correctly.
3.- Confirm Reference Switching (if used)
- Check the Digital Input Map.
- Ensure the correct digital input activates the intended reference.
- Example: If using a Hand/Off/Auto switch on DI3:
- Verify DI3 changes state when switching modes.
- Measure ~24 VDC between DI3 and COM when active.
- Example: If using a Hand/Off/Auto switch on DI3:
4.- Check for Preset Speed Override
- Navigate to:
Complete Settings → Generic Functions → Preset Speeds - Ensure no preset speed is overriding the analog reference.
5.- Review Auto/Manual or PID Reference Settings
- If configured, confirm the correct input is selected for speed reference.
- Verify associated digital inputs are switching properly.
6.- Verify Drive Status
- Ensure the drive displays “Run” on the HMI.
- Check for “CLI” (Current Limit) status:
- Indicates the motor is drawing excessive current, preventing normal ramp-up.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.