How can we help you today?

Does Schneider Offer a Keyed Selector Switch 30mm or 22mm in Blister Pack?

Issue:
Does Schneider offer a keyed selector switch 30mm or 22mm in Blister pack?

Product Line:
Push Buttons and Operators

Environment:
XB4, XB5, XB7, 9001K, Selector Switches

Resolution:
Keyed selector switches are not available in blister pack for 22mm or 30mm product lines.

Schneider Electric USA

Explore more
Category:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Category:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings