Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How can you read the PTH Power On Time status word parameter on the ATV660 drive over Ethernet?

Issue:
Reading the PTH Power On Time status word parameter on the ATV660 drive over Ethernet.

Product Line:
ATV660 and ATV960 drive

Environment:
All

Cause:
Wants to read the power on time PTH parameter in the input scanner map

Resolution:
You have to insert the PTH value in Somove using right click on the input table
and insert the PTH value. ( see the attachment file example).

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:Support | Schneider Electric Global (se.com)

Schneider Electric USA

Attachment(s)
1CC36AE3AC93466C.jpg [101.11 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings