How can we help you today?
BCPM’s are reading a incorrect power factor for each phase.
Issue:
BCPM’s are reading a power factor for each Phase A ,B ,C as 0.9, 0.6, and 0.3 respectively; however the power factor should be roughly 0.9 for all 3 phases.
Product Line:
BCPM
Cause
Voltage Taps and the Incoming CTs have been checked but have not yielded any results as to what could cause the power factor discrepancy on each phase.
Resolution
Resolution is to check the register for 62017 which is a user defined setting which handles the phase assignment being enabled/disabled.
Changing the bit value 0 of register 62017 from 1 to 0 disables this feature.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.