How Do I Configure an ATV630 or ATV930 Drive for PID Auto/Manual Control Using an HOA Switch?
Resolution:
To configure PID Auto/Manual operation with an HOA switch:
-
Navigate to: [Complete Settings] → [Pump Functions] → [PID Controller] → [Reference Frequency]
-
Configure the PID reference:
- Set Internal PID Reference = No.
- The drive will use FR1 as the PID setpoint source.
- Set FR1 = AI1 (Speed Potentiometer).
-
Configure the Auto/Manual selection:
- Assign PAU (Auto/Manual Assignment) to a digital input, for example DI3.
- Set the Manual Reference Assignment to AI1 (Speed Potentiometer).
Operation
Hand (Manual) Mode
- DI3 = High
- The drive speed reference is taken directly from the AI1 potentiometer.
- The drive operates in manual speed control.
Auto Mode
- DI3 = Low
- The drive operates using PID control.
- The PID setpoint is provided by the AI1 potentiometer.
- The drive adjusts output based on PID feedback to maintain the desired process value.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.