Why Does an S-Flex (SFD212) with Bypass Freewheel to a Stop Instead of Following the Deceleration Ramp Time?

Resolution:

When an S-Flex (SFD212) drive with a bypass configuration receives a stop command, it does not follow the programmed deceleration ramp time (DEC). Instead, the motor performs a freewheel (coast) stop.

Why This Happens

When the stop command is issued:

  1. The Drive Output Contactor (DOC) opens immediately.
  2. This causes the run permissive signal on terminal R (when F112 = 1) to be removed.
  3. The motor is disconnected from the VFD output.
  4. Since the drive is no longer controlling the motor, the programmed deceleration ramp cannot be applied.
  5. The motor coasts to a stop based on its inertia and load conditions.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings