How can we help you today?
Can TCSESU switches work as a ring along with TCSESM switches
Question:
Can TCSESU switches work as a ring along with TCSESM switches?
Answer:
Yes.
The TCSESU will forward RSTP BPDUs even it is an unmanaged switch. The both TCESM will therefore recognize the connections and the unmanaged TCSESUs as a "cable" only. Therefore it will not get a loop, but if a connection between TCSESUs fails RSTP failover will take longer as expected because a linkdown is not detected by RSTP.
Therefore generally we do not recommend such a topology.
Can TCSESU switches work as a ring along with TCSESM switches?
Answer:
Yes.
The TCSESU will forward RSTP BPDUs even it is an unmanaged switch. The both TCESM will therefore recognize the connections and the unmanaged TCSESUs as a "cable" only. Therefore it will not get a loop, but if a connection between TCSESUs fails RSTP failover will take longer as expected because a linkdown is not detected by RSTP.
Therefore generally we do not recommend such a topology.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.