How can we help you today?

How to Configure a Third Stage of Neutral Voltage Displacement Protection (59N) on a Powerlogic P3 protection relay

Issue

The device provides only two dedicated stages of neutral voltage displacement (59N), but the customer requires three stages.

Product

Powerlogic  P3 protection relay

Environment

Protection function configuration – Neutral Voltage Displacement (59N)

Cause

The standard protection package includes only two predefined 59N stages. Additional stages must be configured manually using programmable protection stages.

Resolution

To add a third 59N stage:

  1. Activate one of the eight programmable stages available in the device.
  2. Set the input coupling to Uo.
  3. Configure the threshold and settings in the same manner as one of the dedicated 59N stages.
  4. Save and apply the configuration.

This provides functionality equivalent to an additional 59N stage.

Schneider Electric USA

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.